iC5
The IC5 is a simple single phase frequency inverter up to 2.2 kW. Low cost, performance and versatility are the main advantages of the IC5.
One-Phase 230V
- 0,4 kW
- 0,75 kW
- 1,5 kW
- 2,2 kW
Three-Phase 3x 200…230V
0 – 400 Hz
V/F (linear, square, adjustable)
Sensorless vector
- 0,01 Hz (digital)
- 0,06 Hz/60 Hz (analog)
- 0,01 % from the maximum output frequency (digital)
- 0,1% (analog)
- 150% for 1 minuto
- 200% for 30s
- manual (0-15%)
- automatically
Operator control: keyboard, terminal, communications
Frequency Tuning: Analog (0-10V / 4-20mA),
Digital (Keyboard), RS485 Communication (ModBus-RTU)
Start signal: forward / backward
Multi-step operation: up to 8 speeds (multifunction terminal)
Multi-step Acceleration / Deceleration: 0.1 - 6000s, maximum of 8 different types.
Choice of accelerator type: linear, U and S. Emergency stop:
Interrupt the output of the frequency inverter Jog: Jog function Error reset: when the protection function is activated
Performance display and fault display: frequency detection, overload alarm, deadlock, overvoltage, under voltage, overheating, operation, shutdown, constant speed, speed search, output errors (relay and open collector output)
Indicator: Selectable from one of the following: output frequency, current, voltage, DC voltage
Working functions: DC braking, frequency limits, frequency hopping, other function, slip compensation, anti-reverse operation, automatic restart, PID control.
Options: overvoltage, under voltage, overcurrent, drive overheating, motor overheating, phase loss, faulty connection, overload, internal device failure, loss of speed command, hardware failure, communication error, CPU error
Alarms: deadlock, overload Temporary
Power Loss: Less than 15 ms - continues; more than 15 ms automatic restart
- output frequency
- flow
- tension
- frequency set
- speed
- DC voltage
- last 5 errors
Operating temperature: -10 - 50 ° C
Storage temperature: -20 - 65 ° C
Humidity: 90% maximum, non-condensing
Altitude and vibration: max. 1000m, max 5.9m / s2 (0.6g)
Working atmosphere: free of corrosive or flammable gases, oil mist and dust Pressure: 70-106 kPa